Life Safety Update
State Fire Marshal has provided a
memo regarding Personal Electrical Devices in long term care settings under the preview of the Life Safety Code. This memo clarifies that residents will be able to use personal electronics (such as lamps, laptops and phone chargers) within six feet of the bed without being in violation of Section 10.4.2.2 of the Life Safety Code. These devices no longer require a three-prong or double insulated designation. Facilities must conduct an annual visual inspection and document that devices are in proper working order and are not in need of repair. An inspection must also be conducted when a resident moves in or moves to a new room within the facility. These devices can be plugged directly into the wall or into an approved power tap (60601-1 or 1363A). Extension cords and unapproved power strips should still be avoided. We appreciate the continued follow up on this concern and the willingness of the Fire Marshal to update the understanding of the use of personal electronics in long-term care settings.